Backflow

Backflow preventer testing in DC: which sprinklered homes need it and what the test involves

The letter arrives from DC Water, usually addressed to a condo association or a two flat owner, and it says a backflow assembly on the property is due for its annual test. Half the people who get it do not know they have one. The other half know, and are not sure whether the brass thing on the sprinkler riser is the device in question or whether the plumber who handles the irrigation valve can do it. This article sorts out what a backflow preventer is doing on a residential sprinkler system, which DC buildings carry a testing obligation, what the test looks like, and what happens when it fails.

What the device is protecting

Water in a sprinkler pipe sits still for years. It picks up iron from the pipe, loses its chlorine, and in a system with any organic material can grow things you would not want in a glass. If pressure in the street drops, from a main break or a hydrant being used nearby, the pipe in your basement can briefly become the higher pressure side, and stagnant water gets pushed back toward the main. A backflow preventer is a valve arrangement that only lets water move one way. DC Water cares because the drinking water main serves your neighbors too, and the cross connection control program exists to keep every private system from becoming a path back into it.

Which DC homes actually have one

This is where the rowhouse and the condo diverge. DC Water lists fire sprinklers among the cross connections that need a backflow preventer or an air gap, and its regulations put the choice of device in the utility’s hands. A single family house on an NFPA 13D system that shares the domestic service sits at the low end of that range, and whether it gets a simple check valve or a testable double check assembly is settled when the water service and sprinkler plans go in. Ask at that point, not after the pipe is in the wall.The exception is any 13D system that uses antifreeze in an unheated space or has any additive in the pipe, which moves it into a higher hazard category and generally calls for a testable assembly.

A 13R building, which in DC means the three unit conversion, the small condo, and the four story walk up, is different. Those systems nearly always feed through a double check assembly on a dedicated fire line, sometimes a reduced pressure assembly if the water purveyor asked for one, and those assemblies come with a test tag and an annual test requirement. If the DC Water letter came to your association, this is almost certainly why.

How to tell which you have: look at the sprinkler riser in the basement. A testable assembly has two shutoff valves with a body between them carrying four small test ports with caps. A plain check valve has none of that. If there is a tag with a date and a tester’s name hanging from it, you have an assembly and it has a history.

What the annual test involves

The test takes a certified tester about half an hour on a residential assembly. The tester connects a calibrated differential gauge to the test ports, closes the downstream valve, and reads whether each check holds the pressure difference the standard requires. On a reduced pressure assembly the relief valve is also tested for the point at which it opens. The tester files the results with DC Water through the utility’s online backflow portal, and only testers on DC Water’s approved provider list can submit them, so check that list before you hire. A new tag goes on the device.While the downstream valve is closed the sprinkler system is briefly without supply, which is a few minutes in a house and worth telling residents about in a condo. The device goes back in service before the tester leaves.

For sprinklered buildings the test is usually bundled with the annual sprinkler inspection, since the same visit already has someone at the riser. The inspection intervals article lays out what else that visit covers for a 13R building. We do both on one ticket with the paperwork filed, priced as a flat rate visit on the inspections and repair page.

What fails, and what it costs to fix

Three failures account for most red tags on residential assemblies in the District. The first check does not hold because debris from the main is caught on the seat, which is common on older streets and after any nearby main work. A rubber disc has hardened, which is age. Or the relief valve on a reduced pressure assembly weeps, which is the device doing its job on a failing first check. All three are repair kit fixes on a device that is otherwise sound, and a tester who carries the kit can often rebuild and retest in the same visit. Replacing the whole assembly is rare unless the body is cracked from freezing, which brings up the next point.

We do not print a repair price here because the kit cost depends on the make and size of the assembly, and because a rebuild on a device installed in 2008 sometimes turns into a replacement when the body will not seal. What we do promise is a written number before the work, and a retest included in the repair.

Freezing, and the DC basement problem

Backflow assemblies have to be accessible for testing and they cannot be in a space that freezes. Rowhouse front cellars with the old coal chute, the area under an unheated front porch, and the utility room that shares a wall with an open areaway all get cold enough in a January cold snap to crack a brass body. If the assembly is in one of those spots, insulating the room or moving the device is cheaper than replacing it after the thaw. This is the single most useful thing a tester can tell you in September.

What happens if the test is not done

DC Water works by written notice with deadlines, and its regulations let the utility terminate water service to a property that poses an imminent hazard to the public supply. In practice on a residential building it rarely gets that far, but the paper trail lands on the association or the owner, and an untested assembly shows up on the resale inspection for a condo unit as an open item the buyer’s lender asks about.The other cost is the one nobody sees: a device that has not been tested in five years is a device with no evidence it works, and the whole point of the thing is a day when it has to.

For 13D houses: the question to ask at install

If you are having a sprinkler system put into a house or an English basement conversion under the ADU rules, ask at design time whether the connection will use a testable assembly or a plain check. A testable assembly adds a small cost and a recurring annual obligation. A plain check, where DC Water accepts it, has neither. Where the water service is being upsized anyway, DC Water’s own review of the service connection may settle the question for you, which is one more reason to get the service sizing answer early. Either way the choice belongs in the drawings that go to DOB, not in a change order after the riser is set.

Quick checklist

  1. Find the riser and look for four capped test ports between two valves. No ports, no annual test.
  2. Read the tag. If the last date is more than a year back, the test is due.
  3. Check the room for freeze risk before winter.
  4. Keep the filed test report with the sprinkler inspection record. Resale and insurance both ask for it.